Ocular and respiratory symptoms among lifeguards at a hotel indoor waterpark resort.
cross_sectional · Level IV
Where this comes from
- Record sourced from PubMed, PMID 20134344.
- Also identified by DOI 10.1097/JOM.0b013e3181cf00d5.
- No licence information is recorded for this record.
- Because redistribution is not established, this page shows the abstract only. Follow the links below for the full text.
Abstract
To determine the cause of eye and respiratory irritation symptoms among lifeguards at an indoor waterpark. Investigators 1) performed environmental sampling for chloramine, endotoxin, and microbials; 2) administered symptom questionnaires; 3) reviewed ventilation system designs; and 4) reviewed water chemistry. Airborne trichloramine concentrations were found at levels reported to cause irritation symptoms in other studies. Some endotoxin concentrations were found at levels associated with cough and fever in previous studies. Exposed lifeguards were significantly more likely to report work-related irritation symptoms than unexposed individuals. The ventilation system may not have provided sufficient air movement and distribution to adequately capture and remove air contaminants at deck level. No water microbes were detected, and water chemistry met state standards. Indoor waterparks need to control water chemistry and ensure adequate air movement and distribution to control air contaminants and reduce health symptoms.
Medical subject headings
- Eye Diseases
- Health Resorts
- Occupational Exposure
- Respiratory Tract Diseases
- Swimming Pools