Localization of mechanical and electrical defects in dry-type transformers using an optimized acoustic imaging approach.
biomechanical · Level V
Where this comes from
- Record sourced from PubMed, PMID 37976249.
- Also identified by DOI 10.1371/journal.pone.0294674 and PMC identifier 10655985.
- No licence information is recorded for this record.
- Because redistribution is not established, this page shows the abstract only. Follow the links below for the full text.
Abstract
This paper presents an acoustic imaging localization system designed to pinpoint common defects in dry-type transformers by analyzing the unique sounds they produce during operation. The system includes an optimized microphone array and an improved multiple signal classification algorithm. Sound signal characteristics of typical defects, such as foreign object intrusion, screw loosening, and partial discharge, are investigated. A 64-element, 8-arm spiral microphone array is designed using a particle swarm optimization algorithm. The multiple signal classification algorithm enhances acoustic imaging quality in field environments by transforming the input from time-domain to preprocessed frequency-domain signals. The power spectra of subarray and main array are combined, forming the optimization algorithm's output. Experimental results demonstrate the system's effectiveness and accuracy.
Medical subject headings
- Acoustics
- Sound