Variance in multi-blade induced lightning overvoltages among different wind farm topologies.
biomechanical · Level V
Where this comes from
- Record sourced from PubMed, PMID 39236026.
- Also identified by DOI 10.1371/journal.pone.0308449 and PMC identifier 11376563.
- No licence information is recorded for this record.
- Because redistribution is not established, this page shows the abstract only. Follow the links below for the full text.
Abstract
The impact of the topological formation of wind farms upon the lightning induced overvoltages injected into the grid was not covered earlier in literature. However, this topic is highly important to be investigated to allow the usage of the most reliable topology against lightning strikes. For such reason, the paper investigates this point with consideration of most damaging cases as lightning strikes to multi-blades. The testing used ATP software for four main topologies, radial, single-sided ring SSR, double sided ring and star topology. The features defining the similarities in response and the variance range between these topologies were recorded and analyzed. The multi-blade strikes gave an expected increase of 15% to 100% in the injected overvoltage to the grid for all topologies. The star topology showed the most reliable performance by allowing the least injected overvoltage to the grid. The percentage of reduction in the magnitude of the injected overvoltages reached 50.78%, 66.07% and 89.04% for SSR, DSR and star topology respectively with respect to radial topology. Recommendation was provided for design engineers to consider star topology during design phase in terms of more reliable lightning protection.
Medical subject headings